Modbus Poll Rate Estimator

Estimate the minimum Modbus polling cycle time for a given number of registers, baud rate and device count.

Modbus poll rate scan time cycle time response time baud rate polling

Input values

Enter values and click Calculate to see results here.

Formula

T_frame = (Req_bytes + Resp_bytes) × 11 / baud T_total = N_devices × (T_frame + T3.5 + T_response)

Worked Example

Given: 3 devices on one RS-485 bus at 9600 baud. Reading 10 holding registers each. Response time 50 ms.

Step 1: Request: 8 bytes (addr + FC + start + count + CRC) = 8 × 11/9600 = 9.17 ms

Step 2: Response: 25 bytes (addr + FC + byte count + 20 data + CRC) = 25 × 11/9600 = 28.6 ms

Step 3: Per device: 9.17 + 28.6 + 4.0 (T3.5) + 50 = 91.8 ms

Step 4: Total: 3 × 91.8 = 275 ms → 3.6 Hz poll rate

Engineering Notes

  • Bottleneck: The baud rate is usually the bottleneck. At 9600 baud, a 25-byte response takes ~26 ms. At 115200 baud, it takes ~2.4 ms.
  • Batch reads: Reading 100 registers in one request is faster than 10 requests of 10 registers. The per-request overhead is significant.
  • Device count: Each device on an RS-485 bus adds its response time to the total scan time. Limit devices per bus to keep scan time acceptable.
  • Response time: Check the device datasheet for response time. Some devices need 100+ ms to process requests.
  • Timeout: Set the master timeout to 3-5× the expected response time to account for noise and retries.

References

  • MODBUS over Serial Line Specification V1.02